SAFETY DISCLAIMER: This calculator is for estimation and education only. It is NOT a substitute for a licensed electrician or the National Electrical Code as adopted by your local authority having jurisdiction (AHJ). Wire sizing depends on factors this tool may not capture — ambient temperature, number of conductors in raceway, conduit fill, termination ratings, derating factors, and local code amendments. Incorrect wire sizing can cause fire or electrocution. Always have your wiring designed, installed, and inspected by a licensed electrician. Your inputs never leave your browser.

Wire Size Calculator

Find the correct AWG conductor size using NEC 2023 ampacity and voltage-drop calculations. Copper or aluminum • Single-phase or three-phase • Your inputs never leave your browser.

Inputs

Min AWG by Ampacity
Min AWG for Voltage Drop
Recommended AWG
Actual Voltage Drop
SAFETY REMINDER: This tool provides estimates only. Always verify wire sizing with a licensed electrician before installation. Obtain a permit. Incorrect wire sizing can cause fire or electrocution.

NEC 2023 Table 310.16 — 75°C Ampacity Reference

Allowable ampacities from NEC 2023 (NFPA 70) Table 310.16, 75°C column. Conditions: insulated conductors in raceway or cable, not more than 3 current-carrying conductors, 30°C (86°F) ambient. Values cross-verified against published references as of June 2026. Note: Per NEC 240.4(D), 14 AWG copper is limited to 15 A overcurrent protection, 12 AWG copper to 20 A, 10 AWG copper to 30 A, 12 AWG aluminum to 15 A, and 10 AWG aluminum to 25 A — regardless of the higher 75°C Table 310.16 ampacity shown — this calculator applies those NEC limits when recommending a size. The minimum branch-circuit conductor is 14 AWG copper / 12 AWG aluminum per NEC 310.3(B); many electricians and jurisdictions also avoid small aluminum for branch circuits, so verify with your AHJ.

AWG Size Copper 75°C (A) Aluminum 75°C (A) Circular Mils
14 AWG204,107
12 AWG25206,530
10 AWG353010,380
8 AWG504016,510
6 AWG655026,240
4 AWG856541,740
3 AWG1007552,620
2 AWG1159066,360
1 AWG13010083,690
1/0 AWG150120105,600
2/0 AWG175135133,100
3/0 AWG200155167,800
4/0 AWG230180211,600

Source: NEC 2023 (NFPA 70) Table 310.16. Circular-mil values from Engineering Toolbox AWG reference table, cross-checked against LearnMetrics AWG-to-Circular-Mils chart. Both verified June 2026. Data is re-expressed as a lookup table — not a verbatim reproduction of the NFPA 70 table. Always consult the official NEC edition adopted in your jurisdiction.

Frequently Asked Questions

What NEC table does this calculator use?

This calculator uses NEC 2023 (NFPA 70) Table 310.16, specifically the 75°C column for insulated conductors in raceway or cable with not more than three current-carrying conductors at 30°C (86°F) ambient. Under NEC 110.14(C), the conductor ampacity used for a circuit cannot exceed the lowest temperature rating of any connected termination, conductor, or device. For circuits rated 100 A or less (or 14 AWG through 1 AWG), 110.14(C)(1)(a) defaults to the 60°C column unless the equipment is listed for 75°C (or higher) conductors — most modern equipment is, so the 75°C column is the one most commonly used in practice.

What is the "continuous load" toggle?

Per NEC 210.20(A) and 215.3, a continuous load (energized 3+ hours continuously) must be limited to 80% of the breaker/wire rating. Enabling this toggle applies the NEC 125% inverse factor (210.20(A)) to your load amps before finding the minimum wire size — the same effect as the 80% rule.

What is voltage drop and why does 3% matter?

Voltage drop is the loss of voltage along a wire due to its resistance. Per NEC 210.19(A) informational notes, at 3% drop on a 120 V branch circuit the device at the end sees 116.4 V. The NEC recommends (but does not mandate) a maximum of 3% voltage drop on branch circuits and 5% total from service to outlet. This calculator defaults to 3% for branch circuits.

Why does the calculator recommend the larger of two sizes?

Wire must satisfy two independent requirements: it must be large enough to carry the current safely (ampacity), and large enough to keep voltage drop within your target. Either constraint may be the binding one depending on run length. The recommended size is the larger of the two — the conservative, safe choice.

Can I use aluminum wire for branch circuits?

Aluminum is commonly used for service entrance conductors, feeders, and larger circuits. The NEC permits aluminum down to the smaller branch-circuit sizes (NEC 310.3(B) requires 8, 10, and 12 AWG aluminum to be AA-8000-series alloy), but in common practice many electricians and jurisdictions avoid small aluminum and use it only at about 6 AWG and larger. Aluminum requires rated connectors and anti-oxidant compound. Always verify with your local AHJ and a licensed electrician before specifying aluminum.

Does this tool account for conductor derating?

No. This tool gives the base ampacity from NEC Table 310.16 under standard conditions (30°C ambient, ≤3 conductors in raceway). Real installations may require derating for high ambient temperature (NEC Table 310.15(B)(1)), bundled conductors (NEC 310.15(C)), or conduit fill. A licensed electrician must apply all applicable derating factors.

Is this tool free and do I need to sign up?

Yes — completely free, no account required. All calculations happen in your browser. Your inputs never leave your device.