Voltage Drop Calculator
Calculate how much voltage is lost over a wire run and find the minimum AWG to stay within your voltage-drop target. Uses the NEC standard formula (K × I × L / CM). Your inputs never leave your browser.
Inputs
Frequently Asked Questions
Vd = phaseFactor × K × I × L / CM — where phaseFactor is 2 for single-phase or √3 for three-phase, K is the resistivity constant (12.9 for copper, 21.2 for aluminum in ohm-cmil/ft), I is the design current in amps, L is the one-way run length in feet, and CM is the conductor cross-sectional area in circular mils. This formula is standard in NEC handbooks and Ugly's Electrical Reference.
NEC 210.19(A) informational note recommends limiting branch-circuit voltage drop to 3%, and NEC 215.2(A) informational note recommends 3% on feeder circuits, for a combined maximum of 5% from service to outlet. 3% is not an NEC mandate, but it is the widely accepted engineering benchmark.
K ≈ 12.9 ohm-cmil/ft for copper and ≈ 21.2 ohm-cmil/ft for aluminum at 75°C. These values are derived from the resistivity of each material and are widely published in NEC training materials, Ugly's Electrical Reference, and NECA/IBEW references.
Enter the one-way distance from the panel to the load. The formula already accounts for the round-trip current path: the factor of 2 (single-phase) or √3 (three-phase) in the formula accounts for both outgoing and return conductors.
Voltage drop is proportional to run length. On short circuits (under 50 ft at typical household loads), ampacity is usually the binding constraint. On long runs — outdoor lighting, subpanels, EV chargers at the far end of a property — voltage drop becomes the larger wire size driver.
← Back to full Wire Size Calculator • EV Charger Wire Size Calculator →